Evaluación y diseño de planes de emergencia y evacuación ante el riesgo de incendio en instalaciones industriales del sector petrolero

Mostrar el registro sencillo del ítem

dc.contributor.advisor Reyes, Hector es_ES
dc.coverage.spatial Instalaciones industriales del sector petrolero en Neuquén, Argentina ARG es_ES
dc.creator Arnez Parra, Gabriela Analia
dc.date 2025-12-09
dc.date.accessioned 2025-12-29T18:05:43Z
dc.date.available 2025-12-29T18:05:43Z
dc.identifier.uri https://rdi.uncoma.edu.ar/handle/uncomaid/19200
dc.description.abstract La presente investigación evaluó los riesgos de incendio en instalaciones administrativas de una base operativa petrolera mediante metodología integral que combinó análisis cuantitativo, evaluación normativa, investigación cualitativa y simulacro experimental. La evaluación identificó 15 factores de riesgo distribuidos en cuatro categorías, con 40% clasificados como riesgo alto. La carga de fuego obtenida (70720 kcal/m2) corresponde a R2 (riesgo medio) y se mantiene dentro de los parámetros habituales para este nivel. La conformidad con el Decreto 351/79 alcanzó apenas 61%, evidenciando cumplimiento regular, es decir requiere mejoras significativas en medios de escape, sistemas de detección y señalización. La investigación cualitativa reveló que 73% del personal presenta conocimiento procedimental insuficiente, mientras solo 40% recibió entrenamiento práctico en extinción. El simulacro de evacuación evidenció tiempo excesivo (5:30 minutos vs. 4:00 estándar NFPA), identificando limitaciones sistemáticas en la respuesta ante emergencias. Se diseñó un plan de emergencia específico y programa de capacitación estructurado para abordar las deficiencias identificadas. Los resultados evidencian la necesidad de cambios particulares del sistema de gestión de seguridad, incorporando enfoques proactivos que integren aspectos técnicos, humanos y organizacionales para alcanzar estándares apropiados de protección en instalaciones del sector petrolero. es_ES
dc.description.abstract This research assessed fire risks in administrative facilities of a petroleum operational base through comprehensive methodology combining quantitative analysis, regulatory evaluation, qualitative research, and experimental drills. The assessment identified 15 risk factors distributed across four categories, with 40% classified as high risk. The fire load obtained (70720 kcal/m²) corresponds to R2 (medium risk) and remains within the usual parameters for this level. Compliance with Decree 351/79 reached only 61%, demonstrating fair compliance, meaning significant improvements are required in escape routes, detection systems, and signaling. Qualitative research revealed 73% of personnel demonstrated insufficient procedural knowledge, while only 40% received practical extinction training. Evacuation drill evidenced excessive time (5:30 minutes vs. 4:00 NFPA standard), identifying systematic limitations in emergency response. A specific emergency plan and structured training program were designed to address identified deficiencies. The results highlight the need for specific changes to the safety management system, incorporating proactive approaches that integrate technical, human, and organizational aspects to achieve appropriate protection standards in petroleum sector installations. The multi-method approach proved effective for capturing complex interactions between technical vulnerabilities and human factors, providing a replicable framework for similar evaluations in the petroleum industry. es_ES
dc.format application/pdf es_ES
dc.language spa es_ES
dc.publisher Universidad Nacional del Comahue. Facultad de Ciencias del Ambiente y la Salud es_ES
dc.rights Atribución-NoComercial-CompartirIgual 4.0 es_ES
dc.rights.uri https://creativecommons.org/licenses/by-nc-sa/4.0/ es_ES
dc.subject Plan de emergencia es_ES
dc.subject Evacuación es_ES
dc.subject Incendio es_ES
dc.subject Industria petrolera es_ES
dc.subject Extintor es_ES
dc.subject Carga de fuego es_ES
dc.subject Gestión de riesgo es_ES
dc.subject Risk management es_ES
dc.subject Fire protection es_ES
dc.subject Petroleum sector es_ES
dc.subject Emergency plan es_ES
dc.subject.other Ciencias de la Tierra y Medio Ambiente es_ES
dc.title Evaluación y diseño de planes de emergencia y evacuación ante el riesgo de incendio en instalaciones industriales del sector petrolero es_ES
dc.type TesisdePostgrado es
dc.type doctoralThesis eu
dc.type acceptedVersion eu
unco.tesis.grado Especialista en Higiene y Seguridad en el Trabajo es_ES
dc.description.fil Fil: Arnez Parra, Gabriela Analia. Universidad Nacional del Comahue. Facultad de Ciencias del Ambiente y la Salud; Argentina. es_ES
dc.subject.cole Tesis de Posgrado es_ES


Ficheros en el ítem

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem

Atribución-NoComercial-CompartirIgual 4.0 Excepto si se señala otra cosa, la licencia del ítem se describe como Atribución-NoComercial-CompartirIgual 4.0